LTV VALVE APPLICATION INSTRUCTIONS FOR
LOW TEMPERATURE PROTECTION
COPPER-FIN AND POWER-FIN MODELS
CB 495 - 2066 / CH 401 - 2071 AND PB 501 - 2000
INS7238 Rev C
Kit components:
VAL30000 - 1 1/2" VALVE
Models: CB 45 - 500
VAL20000 1 1/2" LTV Valve
• INS7238 Instruction Sheet
VAL3048 - 2" VALVE
Models: CB 495 - 745 and CH 401 - 751
• VAL2123 2" LTV Valve
• INS7238 Instruction Sheet
VAL3047 - 2 1/2" VALVE
Models: CB 986 - 2066, CH 991 - 2071, and PB 501 - 2000
VAL2124 2 1/2" LTV Valve
BLT2118 Bolt (12)
BLT2119 Nut (12)
BLT2026 Flat Washer (24)
BLT2120 Star Washer (12)
GKT2055 Gasket (3)
TFL2092 Flange (3)
• INS7238 Instruction Sheet
CAUTION
Pump and motor unit are designed to be
supported by the inline piping only. Do not
support in any other manner. When placing
pump between flanges, tighten flange bolts
evenly and do not tighten excessively.
Figure 2_ 2" Valve
A = BLENDED
WATER
B = FROM
BOILER
OUTLET
C = SYSTEM
RETURN
WATER
Figure 3_ 2 1/2" Valve
A = BLENDED
WATER
B = FROM BOILER
OUTLET
C = SYSTEM
RETURN
WATER
Figure 1_ 1 1/2" Valve
A = BLENDED
WATER
B = FROM BOILER
OUTLET
C = SYSTEM
RETURN
WATER
NOTE: A-B-C is noted on the valve to depict proper orientation.
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - Kit components:

LTV VALVE APPLICATION INSTRUCTIONS FOR LOW TEMPERATURE PROTECTIONCOPPER-FIN AND POWER-FIN MODELS CB 495 - 2066 / CH 401 - 2071 AND PB 501 - 2

Page 2 - Typical piping applications:

2 of 8Typical piping applications:Figure 4_Primary/Secondary Piping of a Single Boiler - 1 1/2" ValveFigure 5_Primary /Secondary Piping of Multip

Page 3 - INS7238 Rev C

3 of 8Typical piping applications (cont.):Figure 6_Primary /Secondary Piping of a Single Boiler - 2" ValveFigure 7_Primary/Secondary Piping of Mu

Page 4 - Note: Valve must be installed

Typical piping applications (cont.):Figure 8_Primary/Secondary Piping of a Single Boiler - 2 1/2" ValveFigure 9_Primary/Secondary Piping of Multi

Page 5

Figure 11_2" LTV Valve - Up to 750,000 Btu/hrFigure 12_2 1/2" LTV Valve - 990,000 Btu/hr and upFigure 10_1 1/2" LTV Valve - 45,000 - 50

Page 6 - Maintenance instructions

Figure 14_2" - Flow vs. Pressure Drop Figure 15_2 1/2" - Flow vs. Pressure Drop FLOW vs. PRESSURE DROPFLOW IN U.S. GPMPressure Drop, PSIDFig

Page 7

7 of 8INS7238 Rev CNotes

Page 8

Revision Notes: Revision A (INS7238 Rev A)reflects the addition of the 1 1/2" valve.Revision B (INS7238 Rev B) reflects theaddition of the mainte