Copper-fin II/IIE
Boiler, Water Heater
and Pool Heater
Service Manual
Models: 402 - 2072
(Boiler & Water Heater)
Models: 502 - 2072
(Pool Heater)
This manual must only be used
by a qualified heating installer
/ service technician. Read all
instructions, including this
manual and the Installation
and Operation Manual, before
installing. Perform steps in the
order given. Failure to comply
could result in severe personal
injury, death, or substantial
property damage.
WARNING
Save this manual for future reference.
C(F,H,P)X-SER Rev A
Page view 0
1 2 3 4 5 6 ... 43 44

Summary of Contents

Page 1 - Service Manual

Copper-fin II/IIE Boiler, Water Heater and Pool HeaterService Manual Models: 402 - 2072 (Boiler & Water Heater) Models: 502 - 2072 (Pool Heater)Th

Page 2 - Contents

1 Service10Sequence of operation Table 1A_(continued from previous page) Sequence of Operation - Space Heating and DHWOPERATION DISPLAY9. If the DHW

Page 3 - Please read before proceeding

11Display panel menu access Table 1B_Use this procedure to access menus from the display panel1 Service (continued)Note:

Page 4 - What is in this manual?

1 Service12Display panel parameter accessCascadeBMSTable 1C_This is a typical example of accessing a parameter, shown for parameter K2, SH pump delay

Page 5

13Parameter tableTable 1D_This table lists SMART SYSTEM control module parameters and where to access them1 Service (continued)MenuSub ItemDescriptio

Page 6

1 Service14Parameter table (continued)Table 1D_(continued from previous page) This table lists SMART SYSTEM control module parameters and where to ac

Page 7

15Viewable and changeable control parametersA: GeneralA1: User codeThe User Code allows the user to access and change a limited number of control para

Page 8

1 Service16B3: SH Maximum set pointThe SH maximum set point sets the maximum water temperature set point that can be used for space heating. The use

Page 9

1 Service (continued)17 Copper-fin II/IIE Boiler, Water Heater and Pool Service ManualE5: SH/DHW switching time (boiler only)When a SH call for heat

Page 10 - 1 Service

1 Service18F3: Maximum SH set pointWhen the outdoor temperature drops to its minimum setting (F1) the water temperature set point will be at this val

Page 11 - 1 Service (continued)

1 Service (continued)19F6: Outdoor air shutdown differentialThe outdoor air shutdown differential parameter is the number of degrees below parameter

Page 12

2Hazard definitionsThe following defined terms are used throughout this manual to bring attention to the presence of hazards of various risk levels or

Page 13

H: Control modesH1: SH controlling sensor (boiler only)The SH controlling sensor parameter selects the sensor the control will use to regulate the boi

Page 14

1 Service (continued)21I: CascadeI1: Cascade addressThe boiler designated as the Leader needs to be programmed with address 0. All the Member boiler

Page 15

22K4: System pump mode (boiler only)The system pump can be configured to operate in one of two modes. “CFH” runs the system pump whenever there is a

Page 16

2 Maintenance23Maintenance and annual startupService technician(see the following pages for instructions)General: • Address reported problems • In

Page 17

24Follow the service and maintenance procedures given throughout this manual and in component literature shipped with the appliance. Failure to perfo

Page 18

2 Maintenance (continued)25Check relief valve1. Inspect the relief valve and lift the lever to verify flow. Before operating any relief valve, ensu

Page 19

262 Maintenance Copper-fin II/IIE Boiler, Water Heater and Pool Service ManualCheck all wiring1. Inspect all wiring, making sure wires are in good c

Page 20

272 Maintenance (continued) Copper-fin II/IIE Boiler, Water Heater and Pool Service ManualAccess to the burner will require the following steps:1. T

Page 21

2 Maintenance28 Copper-fin II/IIE Boiler, Water Heater and Pool Service ManualAdjusting combustion air pressureThe following is a recommended method

Page 22

2 Maintenance (continued)29 Copper-fin II/IIE Boiler, Water Heater and Pool Service ManualPRESSUREREGULATORADJUSTMENT(UNDER CAPSCREW)INLETOUTLETGASVA

Page 23 - 2 Maintenance

Copper-fin II/IIE Boiler, Water Heater and Pool Service ManualPlease read before proceedingInstaller – Read all instructions, including this manual a

Page 24

2 Maintenance Copper-fin II/IIE Boiler, Water Heater and Pool Service ManualInspect and clean the heat exchanger1. Turn off the main electrical powe

Page 25 - 2 Maintenance (continued)

3 Troubleshooting31Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always

Page 26

3 Troubleshooting32FAULT CAUSE CORRECTIVE ACTIONNo Display- No 120 VAC supplied to unit. • Check external line switch, fuse, or breaker.• Check p

Page 27

3 Troubleshooting (continued)33Temperature Resistance Temperature Resistance-50 490,813 20 46,218-40 336,606 30 34,558-30 234,196 40 26,099-20 165,18

Page 28

3 Troubleshooting34FAULT CAUSE CORRECTIVE ACTIONNoisy Operation- Gas supply problem. • Refer to the Gas Connections Section of the Installati

Page 29

3 Troubleshooting (continued)35FAULT DESCRIPTION CORRECTIVE ACTIONGas Pressure SW(Will require a manual reset once the condition has been corrected.)

Page 30

3 Troubleshooting36FAULT DESCRIPTION CORRECTIVE ACTIONNo Flame Ign(Will require a manual reset. Press the RESET button on the SMART SYSTEM display t

Page 31 - 3 Troubleshooting

3 Troubleshooting (continued)37FAULT DESCRIPTION CORRECTIVE ACTIONNo Flame Running(Will require a manual reset once the condition has been corrected.

Page 32

38FAULT DESCRIPTION CORRECTIVE ACTIONManual Reset High Limit(Will require a manual reset once condition has been corrected. Press the RESET button on

Page 33 - Troubleshooting (continued)

3 Troubleshooting (continued)39FAULT DESCRIPTION CORRECTIVE ACTIONLouver Proving(Lockout will reset automatically after 5 minutes or may be

Page 34

4What is in this manual?ServiceThe Copper-fin display• Display panel readout, buttons and their functionsControl module inputs• Control module inputs

Page 35

3 Troubleshooting40FAULT DESCRIPTION CORRECTIVE ACTIONTemp O/Shoot(Lockout will reset automatically after 5 minutes or may be reset immediately once

Page 36

3 Troubleshooting (continued)41FAULT DESCRIPTION CORRECTIVE ACTIONParameters Progr(Will require a manual reset once the condition has been corrected.

Page 37

3 Troubleshooting42FAULT DESCRIPTION CORRECTIVE ACTIONWatch Dog ErrorThe main control board has detected an internal fault.• Cycle main power.• Repl

Page 38

43NOTES

Page 39

Revision Notes: Revision A (ECO #C08226) initial release.C(F,H,P)X-SER Rev A6/11

Page 40

1 Service5MENU/EXITDISPLAY SCREENENTER/RESETTXENSUOIVERPNWODPU• Press to turn heater off or back on• Press to select a menu item• Press after paramet

Page 41

1 Service6SMART SYSTEMCONTROL BOARDLOWVOLTAGECONNECTIONBOARDDHW THERMOSTAT(OPTIONAL)ROOM THERMOSTAT/ZONE CONTROL(OPTIONAL)SYSTEM SUPPLY/ENABLE SENSOR

Page 42

7SMART SYSTEMCONTROLBOARDLOW VOLTAGECONNECTIONBOARDTHREE WAY VALVE(OPTIONAL ON BOILER)(STD ON POOL HEATER)LOUVER RELAYBUILDINGMANAGEMENTSYSTEMRUN TIME

Page 43

1 Service8General OperationHow the appliance operatesThe Copper-fin uses a finned copper tube heat exchanger to transfer heat from the flue products

Page 44 - C(F,H,P)X-SER Rev A

9Sequence of operationTable 1A_Sequence of Operation - Space Heating and DHW1 Service (continued)OPERATION DISPLAY1. The manual reset high limit (op