Lochinvar KNIGHT 399 User Manual Page 22

  • Download
  • Add to my manuals
  • Print
  • Page
    / 76
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 21
Installation & Operation Manual
22
3 General venting
If the boiler combustion air inlet is
located in a laundry room or pool
facility, for example, these areas will
always contain hazardous
contaminants.
To prevent the potential of severe
personal injury or death, check for
areas and products listed in Table 1A,
page 11 before installing the boiler or
air inlet piping.
If contaminants are found, you
MUST:
• Remove products permanently.
—OR—
• Relocate air inlet and vent
terminations to other areas.
WARNING
WARNING
Air contamination
Pool and laundry products and common household and hobby
products often contain fluorine or chlorine compounds. When
these chemicals pass through the boiler, they can form strong
acids. The acid can eat through the boiler wall, causing serious
damage and presenting a possible threat of flue gas spillage or
boiler water leakage into the building.
Please read the information given in Table 1A, page 11, listing
contaminants and areas likely to contain them. If
contaminating chemicals will be present near the location of
the boiler combustion air inlet, have your installer pipe the
boiler combustion air and vent to another location, per this
manual.
Model Description Kit Number
399 - 800
Filter Box Assembly KIT30022
90° Elbow with Screen KIT30053
Table 3F Optional Room Air Kit
WARNING
When utilizing the single pipe method,
provisions for combustion and ventilation
air must be in accordance with Air for
Combustion and Ventilation, of the latest
edition of the National Fuel Gas Code,
ANSI Z223.1, in Canada, the latest edition
of CGA Standard B149 Installation Code
for Gas Burning Appliances and
Equipment, or applicable provisions of the
local building codes.
Page view 21
1 2 ... 17 18 19 20 21 22 23 24 25 26 27 ... 75 76

Comments to this Manuals

No comments