Lochinvar 80 - 285 User Manual Page 48

  • Download
  • Add to my manuals
  • Print
  • Page
    / 76
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 47
Installation & Operation Manual
48
8 Field wiring
System supply sensor
1. By installing the system supply sensor into the supply of
the primary loop, the temperature of the primary supply
can be controlled. The SMART SYSTEM control
automatically detects the presence of this sensor, and
controls the boiler firing rate to maintain the system
supply temperature to the set point (if the outlet sensor
control is currently selected). If it is desired to control the
system return temperature, then program the SMART
SYSTEM control to use the inlet sensor as the controlling
sensor. See the Knight Boiler Service Manual for
instructions on how to use the inlet sensor as the
controlling sensor. When the inlet sensor is programmed
as the controlling sensor, it is vital that the SYSTEM
SUPPLY sensor be installed. DO NOT INSTALL THE
SYSTEM SUPPLY SENSOR INTO THE SYSTEM
RETURN.
2. Connect these terminals to the system supply sensor
(FIG. 8-3).
Boiler management system
1. An external control may be connected to control either
the firing rate or the set point of the boiler. Connect the
Room Thermostat / Zone Control terminals to the enable
output of the external control and connect the 0 - 10 vdc
terminals to the 0 - 10 vdc output of the external control.
2. Make sure the ground terminal is connected to the
ground output terminal of the external control, and the
0 - 10 vdc terminal is connected to the 0 - 10 vdc terminal
of the external control.
Runtime contacts
The SMART SYSTEM control closes a set of dry contacts
whenever the burner is running. This is typically used by
Building Management Systems to verify that the boiler is
responding to a call for heat.
Alarm contacts
The SMART SYSTEM control closes another set of contacts
whenever the boiler is locked out or the power is turned off.
This can be used to turn on an alarm, or signal a Building
Management System that the boiler is down. Note that these
contacts will close momentarily at the end of each call for
heat.
Wiring of the cascade
When wiring the boilers for Cascade operation, select one
boiler as the Leader boiler. The remaining boilers will be
designated as Members. See page 56 “Configuration of the
Cascade” for a detailed explanation of this procedure.
Connect the system supply sensor and outdoor air sensor (if
used) to the Leader boiler. For the Cascade system to work
properly the system supply sensor must be installed. The
location of the system supply sensor should be downstream of
the boiler connections in the main system loop (FIG.s 6-4,
6-6, and 6-8). The system supply sensor should be wired to the
Low Voltage Connection Board at the terminals marked for
the system supply sensor (see FIG. 8-3). The Leader control
will use the water temperature at the system supply sensor to
control the operation of the Cascade.
If outdoor air reset is desired, the outdoor air sensor should be
wired to the Low Voltage Connection Board at the terminals
marked for the outdoor air sensor (FIG. 8-3). If the outdoor
air sensor is connected, the Leader control will calculate the
water temperature set point based on the programmed reset
curve parameters. If the outdoor air sensor is not connected,
the Leader control will maintain the fixed water temperature
set point that is programmed into the control.
If a Thermostat, Zone Control enable output, or Building
Management System enable output are available, it should be
wired to the Low Voltage Connection Board on the Leader
boiler at the terminals marked for the Room
Thermostat/Zone Control (FIG. 8-3). If the boilers are to run
continuously, connect a jumper wire between the R and W
terminals for the Thermostat/Zone Control input. This will
initiate a call for heat on the Cascade.
Communication between the Leader boiler and the Member
boilers is accomplished by using shielded, 2-wire twisted pair
communication cable. Connect one of the twisted pair wires
to terminal A on each of the Low Voltage Connection boards,
and the other wire of the twisted pair to terminal B on each of
the Low Voltage Connection Boards. Connect the shield wires
to one of the shield ground terminals on the Low Voltage
Connection Boards (FIG. 8-3). If more than two boilers are on
the Cascade, daisy chain the wiring from the Sequencing
terminals on the second boiler to the Sequencing terminals on
the third boiler, then from the third to the forth, and so on.
The connections between boilers can be made in any order,
regardless of the addresses of the boilers. Try to keep each
cable as short as possible.
Low gas pressure switch
1. If a switch is provided to detect low gas pressure, remove
the jumper wire from the terminals on the connection
board and connect them to its normally open contacts
(FIG. 8-3).
2. If both a high and low gas pressure switch is used, connect
their respective contacts in series, and connect them to
the terminals on the connection board (FIG. 8-3).
Flow switch
1. A flow switch is used to guarantee flow through the boiler
before allowing it to fire. The flow switch must be
installed in line with the boiler.
2. Connect these terminals to the normally open contacts on
the flow switch (FIG. 8-3).
Page view 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 75 76

Comments to this Manuals

No comments