IINNSSTTAALLLLAATTIIOONN
Continued
Sidewall Fan
The sidewall fan can be mounted on the inside/outside
(depending upon model) with a sidewall vent hood installed on
the exterior wall. The sidewall fan and accessories are included
in a venting kit provided by the appliance manufacturer. See
TABLE–E for kit numbers.
The venting kit includes the sidewall fan, vent hood, tapered
vent adapter, barometric damper, proving switch and all
necessary relays to interlock with the heaters control system.
The tapered vent adapter reduces the vent size at the inlet to the
fan. There should be no reduction in vent diameter from the
pool heaters flue outlet to the sidewall fan. The barometric
damper must be installed on the flue and adjusted to supply a
negative draft within the range of 0.04 to 0.08 inches w.c.
while the pool heater is operating.
Flue Outlet Piping
With this venting option, you must use Type-B doublewall (or
equivalent) vent materials. Vent materials must be listed by a
nationally-recognized test agency for use as vent materials.
Make the connections from the pool heater vent to the sidewall
fan/cap as direct as possible with no reduction in diameter. Use
the National Fuel Gas Code venting tables for doublewall vent
to properly size all vent connectors and stacks. Follow the vent
manufacturers instructions when installing Type-B vents and
accessories, such as firestop spacers, vent connectors,
thimbles, caps, etc.
When planning the venting system, avoid possible contact with
plumbing or electrical wiring inside walls.
The maximum installed length of sidewall vent pipe with
an
induced draft fan must not exceed 100 feet (30.5m) on the
500,000 - 2,070,000 Btu/hr models. Note: Models 990,000 -
2,070,000 are not approved for sidewall venting without a fan.
The maximum installed length of sidewall vent pipe without an
induced draft fan must not exceed 50 feet (15.2m) on the
500,000 - 750,000 Btu/hr models. Subtract 5 feet (1.5m) for
each 90° elbow. Subtract 2.5 feet (0.7m) for each 45° elbow.
Sidewall Venting Termination
The sidewall vent cap must be installed on an exterior sidewall.
The sidewall fan/powered sidewall vent cap and accessories
are included in a venting kit which is furnished by the pool
heater manufacturer in accordance with CSA International
requirements. This venting kit includes the powered sidewall
fan/cap, proving switch and all necessary relays to interlock
with the pool heaters control system.
The sidewall fan/powered vent cap must be interlocked with
the pool heaters control system to start the fan on a call for
heat and prove fan operation before the pool heater fires. Plug-
in and terminal strip connections are provided on the pool
heater for easy connection of the factory supplied vent kit and
control package for the sidewall vent fan.
Sidewall Venting Without Fan
For 500,000 - 750,000 Btu/hr models approved for sidewall
venting without an external power vent fan, you must install
specific vent kits and venting materials. The following is a
detailed explanation of Sidewall Venting Without an External
Fan installation requirements.
Flue Outlet Piping
Venting Guidelines
If using this venting option, a sealed AL29-4C venting system
for flue products is required on all models of this pool heater.
This venting system operates with a positive pressure in the
vent. The internal combustion air blowers generate this
positive pressure which operates the combustion process and
also exhausts the flue products from the building.
This vent system has specific vent material and installation
requirements. Only use listed sealed AL29-4C vent system
materials. Follow all installation requirements. See
TABLE–B, page 11 for proper pipe size for your pool heater.
A list of sealed AL29-4C flue pipe manufacturers is located on
page 22.
Seal all vent joints and seams gas-tight.
Drain Tee Installation
A drain tee must be installed in the vent pipe to collect and
dispose of any condensate that may occur in the vent system.
The drain tee must be installed as the first fitting after the
horizontal ell on the top of the unit (see Figures 22A and 22B).
Plastic drain tubing, sized per the vent manufacturers
instructions, shall be provided as a drain line from the tee. The
drain tubing must have a trap provided by a 3" (7.6cm)
diameter circular trap loop in the drain tubing. Prime the trap
loop by pouring a small quantity of water into the drain hose
before assembly to the vent. Secure the trap loop in position
with nylon wire ties. Use caution not to collapse or restrict the
condensate drain line with the nylon wire ties. The condensate
drain must be routed to a suitable drain for disposal of
condensate that may occur in the direct vent system. Refer to
the condensate drain installation instructions as supplied by the
manufacturer of the vent material.
Commercial Pool Heaters