2. Isolate the pool heater from the gas supply piping system
by closing a manual shutoff valve during any piping
system pressure testing that is equal to or less than 1/2
PSIG (3.5kPa).
3. Test all gas connections for gas leaks before placing the
pool heater in operation.
Gas Piping
To safely operate this pool heater, you must properly size the
gas supply piping. See Tables- J and K for piping and fitting
requirements. Gas pipe size may be larger than pool heater
connection.
On models 500,000 - 750,000 Btu/hr the gas connection to the
pool heaters are 1 1/4" NPT and on models 990,000 -
2,070,000 Btu/hr the gas connections to the pool heaters are
2" NPT.
IMPORTANT: Do not block access to the
electrical cover plate when installing the
sediment trap. The sediment trap must be a
minimum of 12 inches from the pool heater.
Optional gas controls may require routing of bleeds and vents
to the atmosphere, outside the building when required by local
codes.
Note: All secondary regulators MUST BE of the lock-up type
and spaced a minimum of 6' from the appliance.
Connecting Gas Piping to the Pool
Heater
All gas connections must be made with pipe joint compound
resistant to the action of liquefied petroleum (L.P.) and natural
gases. All piping must comply with local codes and
ordinances. Piping installations must comply with approved
standards and practices.
1. Make sure the gas line is a separate line direct from the
meter unless the existing gas line is of sufficient capacity.
Verify pipe size with your gas supplier.
2. Use new, properly threaded black iron pipe free from chips.
If you use tubing, make sure the ends are cut square,
deburred and clean. Make all tubing bends smooth and
without deformation. Avoid flexible gas connections.
Internal diameter of flexible lines may not provide the pool
heater with the proper volume of gas.
3. For ease of service, install a union.
4. Install a manual main gas shutoff valve at the pool heaters
gas inlet, outside of the pool heater in accordance with the
National Fuel Gas Code, ANSI Z223.1, this must be
installed within 6 feet of the pool heater.
Figure 28 – Gas Line Connection
5. Run pipe or tubing to the pool heaters gas inlet. If you use
tubing, obtain a tube to pipe coupling to connect the tubing
to the pool heaters gas inlet.
6. Install a sediment trap in the supply line to the pool
heaters gas inlet (see Figure 28).
7. Apply a moderate amount of good quality pipe compound
(do not use Teflon tape) to pipe only, leaving two end
threads bare.
8. Remove the seal over the gas inlet to the pool heater.
9. Connect the gas pipe to the inlet of the pool heater. Use a
wrench to support the gas manifold on the pool heater.
10. For L.P. gas, consult your L.P. gas supplier for expert
installation.
11. Ensure that all air is completely bled from the gas line
before starting the ignition sequence. Start up without
properly bleeding air from the gas line may require
multiple reset functions of the ignition control module to
achieve proper ignition.
WARNING: Do not have any open flame in
proximity to the gas line when bleeding air from
the gas line. Gas may be present.
Gas Train and Controls
Note: The gas train and controls assembly provided on this
pool heater have been tested under the applicable American
National Standard to meet minimum safety and performance
criteria such as safe lighting, combustion and safety shutdown
operation.
Installation and Service Manual